CnT input
Unit
(Case A)
Unit
(Case B)
OFF
OFF
*ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Note (1) The ON with the * mark indi-
cates an ON operation using the
wired remote control, etc.
*ON
(i) Level input
If the factory settings (Jumper wire J1 external input on the PCB of indoor unit) are set, or “LEVEL INPUT” is se-
lected in the wired remote control’s indoor unit settings.
1) Input signal to CnT OFF
→
ON Air-conditioner ON
2) Input signal to CnT ON
→
OFF Air-conditioner OFF
(ii) Pulse input
When Jumper wire J1 on the PCB of indoor unit
is cut at the field or “PULSE INPUT” is selected in the wired remote
control’s indoor unit settings.
Input signal to CnT becomes valid at OFF
→
ON only and the motion of air-conditioner [ON/OFF] is inverted.
CnT input
Unit
(Case A)
Unit
(Case B)
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
(19) Hot keep operation
During the heating operation, the indoor fan speed can be is controlled based on the temperature of the indoor heat exchanger
(Th2) to prevent blowing out of cold air.
(20) Frost prevention control
(a) Operating conditions
(b) Detail of anti-frost operation
(c) Reset condition
Indoor heat exchanger
temperature (ºC)
2.5
8
Operation mode
Item
Protective control
Reset
Compressor operation
Indoor fan
Forced outage
Operation instruction
Depends on operation mode
2.5
(i)
Reset
Protective
control
8
(ii)
-
159
-
'16 • SCM-T-199
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...