(1) Switching sequence of the operation mode switches of remote control
DRY
COOL
FAN
HEAT
AUTO
(2) [CPU reset]
This functions when “CHECK” and “GRILL” buttons on the remote control are pressed simultaneously. Operation is same
as that of the power source reset.
(3) [Power failure compensation function]...Electric power source failure
• This becomes effective if “Power failure compensation effective” is selected with the setting of remote control function.
• Since it memorizes always the condition of remote control, it starts operation according to the contents of memory no
sooner than normal state is recovered after the power failure. Although the auto swing stop position and the timer mode
are cancelled, the weekly timer setting is restored with the holiday setting for all weekdays.
After recovering from the power failure, it readjusts the clock and resets the holiday setting for each weekday so that the
setting of weekly timer becomes effective.
• Content memorized with the power failure compensation are as follows.
Note (1) Items
➅
,
➆
and
➇
are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is
cancelled regardless whether the power failure compensation is effective or not.
➀
At power failure – Operating/stopped
If it had been operating under the off timer mode, sleep timer mode, the state of stop is memorized. (Although
the timer mode is cancelled at the recovery from power failure, the setting of weekly timer is changed to the
holiday setting for all weekdays.)
➁
Operation mode
➂
Airflow volume mode
➃
Room temperature setting
➄
Louver auto swing/stop
However, the stop position (4-position) is cancelled so that it returns to Position (1).
➅
“Remote control function items” which have been set with the remote control function setting (“Indoor function
items” are saved in the memory of indoor unit.)
➆
Upper limit value and lower limit value which have been set with the temperature setting control
➇
Sleep timer and weekly timer settings (Other timer settings are not memorized.)
Master/ slave setting when more than one remote controls are used
A maximum of two remote controls can be connected to one indoor unit (or one group of indoor units.)
Remote control cord (no polarity)
Remote control
SW1 "Master"
Switch
Setting
Contents
M
Master remote control
SW1
S
Slave remote control
Remote control
SW1 "Slave"
Indoor units
Caution
When using multiple remote controls, the following dispiays or settings
cannot be done with the slave remote control. It is available only with
the master remote control.
Louver position setting (set upper or lower limit of swinging range)
Setting indoor unit functions
Setting temperature range
Operation data display
Error data display
Silent mode setting
Test operation of drain pump
Remote control sensor setting
Master
Slave
SW1
SW2
SW1
Board
Upper
Lower
Set SW1 to “Stave” for the slave remote control. It was factory set to “Master” for shipment.
Note: The setting “Remote control thermistor enabled” is only selectable with the master
remote control in the position where you want to check room temperature.
The air-conditioner operation follows the last operation of the remote control regardless of
the master / slave setting of it.
7.4.2 Operation control function by the wired remote control
•
Model RC-E5
[Parts layout on remote control PCB]
X
Y
SW2
SW1
A
B
M
S
親
子
SW1
SW2
-
170
-
'16 • SCM-T-199
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...