2 . Accessories & prepare on site
Item name
Q’ty
Remark
Switch box
For 1 piece or 2 pieces (JIS C 8340 or
equivalent)
1
These are not required when installing
directly on a wall.
Thin wall steel pipe for electric appliance
(JIS C 8305 or equivalent)
As required
Lock nut, bushing (JIS C 8330 or equivalent) As required
Lacing (JIS C 8425 or equivalent)
As required Necessary to run R/C cable on the wall.
Putty
Suitably For sealing gaps
Molly anchor
As required
R/C cable (0.3 mm
2
x 2 pcs)
As required See right table when longer than 100 m
Accessories
R/C main unit, wood screw (ø3.5 x 16) 2 pcs
User’s Manual, Installation Manual
Parts procured at site
When the cable length is longer than
100 m, the max size for wires used
in the R/C case is 0.5 mm
2
. Connect
them to wires of larger size near
the outside of R/C. When wires are
connected, take measures to prevent
water, etc. from entering inside.
< 200 m
0.5 mm
2
x 2-core
< 300 m
0.75 mm
2
x 2-core
< 400 m
1.25 mm
2
x 2-core
< 600 m
2.0 mm
2
x 2-core
3. Remote control installation procedure
Determine where to install the remote control
Installation
“Using a switch box”
“Installed directly on a wall”
Wiring direction “Backward”
“Upper center”, “Upper left”
Cautions for selecting installation place
(1) Installation surface must be flat and sufficiently strong.
R/C case must not be deformed.
(2) Where the R/C can detect room temperatures accurately.
This is a must when detecting room temperatures with
the temperature sensor of R/C.
· Install the R/C where it can detect the average tempera-
ture in the room.
· Install the R/C separated from a heat source sufficiently.
· Install the R/C where it will not be influenced by the
turbulence of air when the door is opened or closed.
Select a place where the R/C is not exposed to direct
sunlight or blown by winds from the air-conditioner or
temperatures on the wall surface will not deviate largely
from actual room temperature.
Installation space
30mm
30mm
30mm
120mm
R/C temperature sensor
Wiring
Secure minimum spaces for
disassembling the case.
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped
screwdriver, 50mm or
more is available.
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...