27
5.2 Output setting for stoppage
5. Automatic Operation and Functions
• The output value to be output just after starting the stop timer is calculated by the following formula (the
maximum value is limited to 100%).
OUT.t=A
×
ST.G / 100 (%)
OUT.t =Control output value just after starting the stop timer (%)
A
=Control output value just before starting the stop timer (%)
ST.G =Stop gain set value (%)
5.1.3
Stop timer and Stop gain setting
- - - - - - - Item number : 10
• In the adjustment mode (power ON with DIP. SW8 OFF), select item number 10, and then set the stop timer
and the stop gain.
• If it is not necessary to correct the inertia while stopping the machine; it is not necessary to change the initial
values.
On the adjustment / setting item selection screen, set the item number to [10],
and then press the
T
key.
• Setting range:
• Stop timer - - - -0 to 30 sec - - Initial value = 0 sec
• Stop gain5 - - - - to 400% - - - - Initial value = 100%
• Normally, set the stop gain to 100% or more at unwinding, and to 100% or less at winding.
5.2
Output setting for stoppage
5.2.1
Switching between manual output 1 and 2
• When the [RUN] signal is OFF, the manual set value 1 will be output.
• When manual output signal 2 is input, the manual set value 2 will be output.
• To switch the manual output signal, select item number 50 in the adjustment mode, and then assign the
functions to the input contact terminals (MI1, MI2, or MI3).- - - - - - - - - - - - - - - - - - - - - -Refer to Sec. 6.1.2
5.2.2
Output memory function
• When the [RUN] input signal is turned OFF while the output memory signal is ON, the output value sent out
just before the [RUN] input signal turning OFF will be stored in the memory. After end of the stop timer, this
memory value will be output during the [RUN] input signal is OFF.
• When the output memory signal is ON, if the [RUN] input signal is repeatedly turned ON and OFF, the
output value sent out at just before final turning-OFF of the [RUN] input signal will be stored in the memory.
• Turning off the power will not reset the memory value.
• When the power is turned ON while the output memory signal is ON, the output value stored in the memory
is output.
• When the [RUN] input signal is turned ON while the output memory signal is ON, automatic control will be
restarted using the output value stored in the memory.
• When the [RUN] input signal is OFF, if the output memory signal is turned OFF, the manual set value 1 or 2
will be output.
• To use the output memory signal, select item number 50 in the adjustment mode, and then assign the
function to the input contact terminal (MI1, MI2, or MI3). - - - - - - - - - - - - - - - - - - - - - - Refer to Sec. 6.1.2.
Adjustment/setting
item selection screen
Содержание LE-30CTN
Страница 1: ...MODEL LE 30CTN Conforming to CE Marking JZ990D33401D INSTRUCTION MANUAL ZJ 4049D ...
Страница 2: ......
Страница 4: ......
Страница 61: ...59 13 4 Measures for EMC 13 EC Directives CE Marking MEMO ...
Страница 63: ......
Страница 64: ...JZ990D33401D TENSION CONTROLLER MODEL LE 30CTN ...