MELSEC-Q
4 DATA USED FOR POSITIONING CONTROL
Pr. 7
Positioning complete signal output time
Set the output time of the positioning complete signal [X8 to XF] output from the
QD70.
Positioning complete indicates that the preset dwell time has elapsed after the
QD70 ended pulse output.
If the setting value is 0 (ms) or if the axis stop signal was used to make a stop
during JOG operation or speed control of speed-position switching control, the
positioning complete signal is not output.
M
[Y8 to YF]
[X18 to X1F]
PLC
CPU
PLC
Positioning
start signal
Positioning
complete signal
Positioning control
Positioning start signal
Positioning start
complete
BUSY signal
Positioning complete signal
Positioning complete signal
(after elapse of dwell time)
Output time
QD70
Positioning complete signal output time
Pr. 8
Deviation counter clear signal output time
Set the duration of the deviation counter clear signal output during an OPR
control operation using any of the following methods: the near-point dog method,
stopper 1 to 3, and count 1. (For details, refer to your drive unit manual.)