8 - 11 8 - 11
MELSEC-Q
8 OPR CONTROL
Restrictions
(1) Always limit the motor torque.
If the torque is not limited, the motor may fail when the machine presses
against the stopper.
(For a torque limit, refer to the manual of the drive unit used.)
(2) Use an external input signal as the zero signal.
Precautions during operation
(1) If the zero signal is input before the workpiece stops at the stopper, the
workpiece will stop at that position, and that position will become the OP.
OPR control start
(Positioning start signal: Y8 to YF)
Creep speed
t
ON
OFF
ON
OFF
OFF
ON
V
Torque limit
Zero signal
Standby
Standby
0
OP address
OPR.5
Deviation counter clear signal output time
Pr.8
Bias speed at start
Pr.6
Deviation counter clear output
Axis operation status
Movement amount after
near-point dog ON
Current feed value
OPR request flag
Status: b0
Md.7
Md.4
Md.2
Md.1
OPR complete flag
Status: b1
Md.7
During OPR
Unfixed
Unfixed
Traveled value is stored
Fig. 8.9 When the zero signal is input before the stop at the stopper
(2) If the axis is started during zero signal ON, the "Zero signal ON" error (error
code: 202) occurs.