7 - 12 7 - 12
MELSEC-Q
7 ONLINE MODULE CHANGE
(c)
Click the [Close] button to close the System monitor screen.
(d)
Referring to (1), set the used channel to conversion enable, and monitor
the digital output values (buffer memory addresses 11 to 14, 54 to 62,
UnvG11 to 14, Un\G54 to 62) to check whether proper conversion has
been made or not.
(e)
Since the new module is in a default status, it must be initialized by a
sequence program after control resumption.
Before performing initialization, check whether the contents of the
initialization program are correct or not.
1)
Normal system configuration
The sequence program should perform initialization on the leading
edge of Module READY (X9) of the A/D converter module.
When control resumption is executed, Module READY (X0) turns ON
and initialization is performed. (If the sequence program performs
initialization only one scan after RUN, initialization is not performed.)
2)
When used on remote I/O network
Insert a user device that will execute initialization at any timing
(initialization request signal) into the sequence program. After control
resumption, turn ON the initialization request signal to perform
initialization. (If the sequence program performs initialization only one
scan after a data link start of the remote I/O network, initialization is not
performed.)