3 - 27 3 - 27
MELSEC-Q
3 SPECIFICATIONS
POINT
When the User range writing request (YA) is turned ON in the normal mode with
A/D conversion enabled, the A/D converter module restores the user range.
Offset/gain setting mode flag (XA)
User range writing request (YA)
User range restoration processing
A/D conversion completed flag
(Buffer memory address 10: Un\G10)
Digital output value
(Buffer memory addresses 11 to 14,
54 to 61: Un\G11 to 14, Un\G54 to 61)
Power of 2-wire transmitter
During restoration
Restoration
completed
Power ON
Power OFF
Power ON
During user range restoration: A/D conversion stop, A/D conversion completed flag
(buffer memory addresses 10: Un\G10) OFF, digital
output value held as previously, power of 2-wire
transmitter OFF (Q62AD-DGH only)
After user range restoration: A/D conversion resumed (when user range setting is
used, A/D conversion is resumed at the restored
offset/gain setting value.)