8 TROUBLESHOOTING
8 TROUBLESHOOTING
The following section explains the types of errors that may occur when the A/D
converter module is used, and how to troubleshoot such errors.
8.1 Error Code List
If an error occurs in the A/D converter module while writing to or reading data from the
PLC CPU, the applicable error code is written to buffer memory address 19 (Un\G19).
Table 8.1 Error code list (1/2)
Error code
(decimal)
Error description
Processing
10
The input range is set an illegal value using the
intelligent function module switch in GX Developer.
indicates the channel number set incorrectly.
Set the correct parameter value in the parameter
setting of GX Developer. (See Section 4.5.)
111
Module error at startup.
Turn the power OFF and ON again. If the error
occurs again, the module may be malfunctioning.
Contact the nearest distributor or branch office
with the description of the problem.
112
The setting of the intelligent function module switch
5 is other than 0.
Set the correct parameter value in the parameter
setting of GX Developer. (See Section 4.5.)
161
1
The G.OGSTOR instruction was executed in the
offset/gain setting mode.
Do not execute the G.OGSTOR instruction in the
offset/gain setting mode.
162
• The G.OGSTOR instruction was executed
consecutively.
• At the time of offset/gain setting, a set value was
written to the E
2
PROM 26 or more times.
• Execute the G.OGSTOR instruction only once
for one module.
• At the time of offset/gain setting, write a set value
only once at one time.
163
The G.OGSTOR instruction was executed for the
model that differs from the model for which the
G.OGLOAD instruction had been executed.
Execute the G.OGLOAD and G.OGSTOR
instructions for the same model.
20
The average time setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
outside the 40 to 5000ms range.
indicates the channel number set incorrectly.
Re-set the average time setting to within 40 to
5000ms.
30
The average count setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
outside the 4 to 500 times range.
indicates the channel number set incorrectly.
Re-set the average count setting to within 4 to 500
times.
31
The move average count setting at any of the buffer
memory addresses 1 to 4 (Un\G1 to Un\G4) is
outside the 2 to 60 times range.
indicates the channel number set incorrectly.
Re-set the move average count setting to within 2
to 60 times.
32
The time constant setting of the primary delay filter
at any of the buffer memory addresses 1 to 4
(Un\G1 to Un\G4) is outside the 10 to 5000 range.
indicates the channel number set incorrectly.
Re-set the time constant setting to within 10 to
5000.
1: Not written to the buffer memory address 19 (Un\G19). Written to the completion status area (S)+1 of the G.OGSTOR
instruction.