3 SPECIFICATIONS
3.4.21 Mode switching setting (buffer memory addresses 158, 159: Un\G158, Un\G159)
(1) Set the values of the mode desired to be switched to.
(2) After setting the values, turning the operating condition setting request (Y9) from
OFF to ON switches to that mode.
(3) When mode switching is performed, this area is cleared to zero and the operating
condition setting completed flag (X9) turns OFF.
After confirming that the operating condition setting completed flag (X9) has
turned OFF, turn OFF the operating condition setting request (Y9).
Set values
Mode to be switched to
Buffer memory address 158
Buffer memory address 159
Normal mode
0964
H
4144
H
Offset/gain setting mode
4144
H
0964
H
POINT
If the values written are other than the above, mode switching is not performed and
only the operating condition is changed.
3.4.22 Pass data classification setting (buffer memory addresses 200: Un\G200)
(Q64AD-GH only)
(1) Areas used to restore the user range settings offset/gain values when online
module change is made.
Refer to chapter 7 for details of online module change.
(2) Specify whether the offset/gain values to be saved/restored are voltages or
currents when saving/restoring the offset/gain values of the user range setting.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
CH4 CH3 CH2 CH1
0
0
0
0
0
0
0
0
Information of b4 to b15 is fixed to 0.
1: Current specified
0: Voltage specified
0
0
0
0
POINT
Refer to Section 4.6 for the offset/gain value setting method.