8 - 4 8 - 4
MELSEC-Q
8 TROUBLESHOOTING
(2) When flashing
Check item
Corrective action
Is an input signal error being generated?
Check the input signal error detection flag (buffer memory
address 49, Un\G49).
8.2.4 When the digital output values cannot be read
Check item
Corrective action
Is 24VDC external supply power being supplied? (Q62AD-
DGH only)
Check that the external supply power terminals (terminal
Nos. 16, 17) are supplied with a 24VDC voltage.
Is there any fault with the analog signal lines such as
disconnection (for the Q62AD-DGH, disconnection of the
signal line with the 2-wire transmitter) or wire break?
Check for faulty condition of the lines visually and perform
a continuity check of the signal lines.
Is the CPU module in the STOP status?
Set the CPU module to the RUN status.
Are the offset/gain settings correct?
Verify that the offset/gain settings are correct
(see Sections 4.6 and 5.6.2).
If the user range is being used, switch to a different default
input range and check if A/D conversion is correctly
performed. If it is correctly performed, redo the offset/gain
settings.
Is the input range setting correct?
Check the buffer memory address 20 (Un\G20) in the
monitor of GX Developer.
If the input range setting is incorrect, redo the GX
Developer intelligent function module switch setting
(see Section 4.5).
Is the A/D conversion enable/disable setting for the
channel that was input set to A/D conversion disabled?
Check the ON/OFF status with buffer memory 0 (Un\G0) in
GX Developer system monitor and review the initial setting
of the sequence program or utility package
(see Section 3.4).
Is a large value set as the A/D conversion starting time
setting?
Check the buffer memory addresses 5, 6 (Un\G5, Un\G6)
in the monitor of GX Developer.
Has the operating condition setting request (Y9) been
executed?
From GX Developer, turn the operating condition setting
request (Y9) from ON to OFF to check that the digital
output values are stored into the buffer memory addresses
11 to 14 (Un\G11 to Un\G14), 54 to 61 (Un\G54 to
Un\G61).
If so, review the initial setting of the Sequence program or
utility package (see Section 3.3).
POINT
The module may be faulty if the digital output values cannot be read after proper
corrective actions have been taken according to the above check items. Consult
the nearest representative or branch.