5 - 24 5 - 24
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-AD)
(3) User range restoration
(a) Set "Voltage specified" or "Current specified" in the Setting value field of
Pass data classification setting, and click the Execute test button.
When the setting is completed, the set data is displayed in the Current value
field of CH Pass data classification setting.
(b) Set the recorded values in the Setting value fields of CH Industrial
shipment settings offset/gain values/user range settings offset/gain values.
(c) Select all the Setting value fields of CH Industrial shipment settings
offset/gain values/user range settings offset/gain values, and click the
Execute test button.
When write is completed, the set values are displayed in the Current value
fields of CH Industrial shipment settings offset/gain values/CH User
range settings offset/gain values.
(d) Change the Setting value field of Pass data write request to "Request", and
click the Execute test button.
Make sure that the indication in the Current value field of Pass data write
request changes from "Request" to "OFF" on completion of write.
Содержание GX Configurator-AD
Страница 2: ......
Страница 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Страница 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Страница 207: ......