3 - 26 3 - 26
MELSEC-Q
3 SPECIFICATIONS
(2) Output signals
Device No.
Signal Name
Description
Y9
Operating
condition setting
request
(1) Turn this signal ON when making any of the following settings valid.
• A/D conversion enable/disable setting (buffer memory address 0: Un\G0)
• CH Average time/Average number of times/Move average/Time constant settings
(buffer memory addresses 1 to 4: Un\G1 to Un\G4)
• CH A/D conversion starting time setting (buffer memory addresses 5, 6: Un\G5,
Un\G6)
• Averaging process specification (buffer memory address 9: Un\G9)
• Input signal error detection/warning output settings (buffer memory address 47:
Un\G47)
• CH process alarm upper/lower limit value (buffer memory addresses 86 to 117:
Un\G86 to Un\G117)
• CH rate alarm warning detection period (buffer memory addresses 118 to 121:
Un\G118 to Un\G121)
• CH rate alarm upper/lower limit value (buffer memory addresses 122 to 137:
Un\G122 to Un\G137)
• CH input signal error detection setting value (buffer memory addresses 138 to 141:
Un\G138 to Un\G141)
(2) See the X9 column for ON/OFF timing.
[In offset/gain setting mode]
(1) This turns ON when the value for the adjusted offset/gain settings are registered in the
A/D converter module.
(2) See the XA column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
YA
User range
writing request
[In normal mode]
(1) This signal turns ON when the user range is restored.
(2) Refer to the field of XA for the ON/OFF timing.
Refer to Chapter 7 for user range restoration.
YB
Channel change
request
(1) This turns ON when changing the channel for which offset/gain settings are to be
performed.
(2) See the XB column for ON/OFF timing.
See Section 4.6 for offset/gain settings.
YC
Offset/gain
change request
1
(1) Turn this signal ON when changing the offset/gain value.
(2) Refer to the field of XC for the ON/OFF timing.
Refer to Section 4.6 for the offset/gain setting.
YD
Maximum
value/minimum
value reset
request
(1) Turning ON the Maximum value/minimum value reset request (YD) clears the maximum
value/minimum value stored at any of the buffer memory addresses 30 to 37, 62 to 77
(Un\G30 to Un\G37, Un\G62 to Un\G77).
(2) See the XD column for ON/OFF timing.
YF
Error clear
request
(1) Turn this signal ON when clearing a write error or input signal error.
(2) Refer to the field of XF or XC for the ON/OFF timing.
1: Q62AD-DGH only
Содержание GX Configurator-AD
Страница 2: ......
Страница 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Страница 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Страница 207: ......