3 - 5 3 - 5
MELSEC-Q
3 SPECIFICATIONS
(1) Input characteristics of Q64AD-GH
(a) Voltage input characteristic
Fig. 3.1 shows a graph of the voltage input characteristic.
1)
2)
3)4)
1
65535(32767)
64000(32000)
0
-64000(-32000)
-1536(-768)
-65536(-32768)
-15
-10
-5
0
5
10
15
Di
g
it
a
l out
pu
t
val
u
e
Analog input voltage (V)
Analog input practical range
The value within parentheses indicates the digital output value (16 bits).
Maximum resolution
Number
Analog input
range setting
Offset
value
Gain
value
Digital output value
(32 bits) 2
Digital output value
(16 bits) 2
32 bits
16 bits
1)
1 to 5V
1V
5V
62.5µV
125.0µV
2)
0 to 5V
0V
5V
0 to 64000
0 to 32000
78.2µV
156.4µV
3)
-10 to 10V
0V
10V
-64000 to 64000
-32000 to 32000
4)
0 to 10V
0V
10V
156.3µV
312.6µV
—
User range setting
(Uni-polar)
1
1
0 to 64000
0 to 32000
—
User range setting
(Bi-polar)
1
1
-64000 to 64000
-32000 to 32000
47.4µV
94.8µV
Fig. 3.1 Voltage input characteristic of Q64AD-GH