7 - 2 7 - 2
MELSEC-Q
7 ONLINE MODULE CHANGE
7.1 Online Module Change Conditions
The CPU, MELSECNET/H remote I/O module, A/D converter module, GX Developer
and base unit given below are needed to perform an online module change.
(1) CPU
The Q12PHCPU or Q25PHCPU is needed.
For precautions for multiple PLC system configuration, refer to the Process CPU
User's Manual (Function Explanation/Program Fundamentals).
(2) MELSECNET/H remote I/O module
The module of function version D or later is necessary.
(3) A/D converter module
The module of function version C or later is necessary.
(4) GX Developer
GX Developer of Version 7.10L or later is necessary.
GX Developer of Version 8.18U or later is required to perform an online
module change on the remote I/O station.
(5) Base unit
1) When the slim type main base unit (Q3 SB) is used, an online module
change cannot be performed.
2) When the power supply module unnecessary type extension base unit
(Q5 B) is used, online module change cannot be performed for the modules
on all the base units connected.
7
Содержание GX Configurator-AD
Страница 2: ......
Страница 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Страница 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Страница 207: ......