MELSEC-Q
3 SPECIFICATIONS
3.4.3 CH Average time/Average number of times/Move average/Time constant settings
(buffer memory addresses 1 to 4: Un\G1 to Un\G4)
(1) Set the average time, average count, move average count or primary delay filter
time constant for each channel specified for averaging processing.
(2) To make the setting valid, the operating condition setting request (Y9) must be
turned ON/OFF. (Refer to Section 3.3.2.)
(3) 0 is set as the default.
(4) The setting ranges are as follows.
Processing method
Setting value
Time averaging
40 to 5000 (ms)
1
Count averaging
4 to 500 (times)
Move averaging
2 to 60 (times)
Primary delay filter
10 to 5000 (ms)
1
1 The value can be set in 1ms increments, but the first digit is discarded and
the value is processed in 10ms increments.
POINT
(1) The channel where the value outside the above setting range has been written
results in an error, the error code is stored into the Error code (buffer memory
address 19: Un\G19), the error flag (XF) turns ON, and the A/D conversion
processing is performed at the pre-error setting.
(2) Since the default setting is 0, change it according to the processing method.
(3) The value, which has been set to the channel specified for sampling
processing, is ignored.
3.4.4 CH A/D conversion starting time setting (buffer memory addresses 5, 6: Un\G5,
Un\G6) (Q62AD-DGH only)
(1) This area is used to set the "time necessary from when the used 2-wire transmitter
powers on until its output stabilizes" on a channel basis.
(2) To make the setting valid, the operating condition setting request (Y9) must be
turned ON/OFF. (Refer to Section 3.3.2.)
(3) The setting range is 0 to 3276.7 seconds (0 to 54 minutes and 36.7 seconds)[0 to
32767].
Set the time in 100ms increments.
Example) When setting the A/D conversion starting time to 5 seconds, store 50
into the buffer memory.
(4) The default is set to 3 seconds [30].
(5) Refer to Section 3.2.5 for details of the A/D conversion starting time setting
function.
POINT
The channel where the value outside the above setting range has been written
results in an error, the error code is stored into the Error code (buffer memory
address 19: Un\G19), the error flag (XF) turns ON, and operation is performed at
the pre-error setting.