7 - 25 7 - 25
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.5 When user range setting is used and initial setting was made with sequence program
(other system is available)
(1) Conversion disable
(a)
Set the A/D conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn operating condition
setting request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the A/D conversion
completion flag (buffer memory address 10: Un\G10), turn off Operation
Condition Setting Request (Y9).
(The screen shows the setting example of the Q64AD-GH.)
Содержание GX Configurator-AD
Страница 2: ......
Страница 23: ...2 6 2 6 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Страница 120: ...5 31 5 31 MELSEC Q 5 UTILITY PACKAGE GX Configurator AD MEMO ...
Страница 145: ...6 25 6 25 MELSEC Q 6 PROGRAMMING MEMO ...
Страница 207: ......