4 - 18
4. CONNECTION TO FUJI PLC
4.5 PLC Side Setting
(1) Setting of the MODE
Make the MODE settings using the MODE switch.
(2) Setting of the station No.
Make the station No. using RS-485 station No.
switches.
(3) Connecting terminating resistors
Turn ON/OFF the terminating resistor using RS-485
terminating resistor ON/OFF switch.
(4) Setting of Stop bit, Data bit, Parity bit, Initializing
method
Make the settings using the character configuration
switches.
(5) Transmission speed settings
Make the settings using the baudrate setting switches.
4.5.5
Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
(1) Direct specification
Specify the station No. of the PLC to be changed when
setting device.
MODE
Switch position
Command-setting-type start-stop
synchronization, nonsequence
format
RS-232C 1:1
1
Command-setting-type start-stop
synchronization, nonsequence
format
RS-232C 1:1,
and RS-485 1:N
2
Command-setting-type start-stop
synchronization, nonsequence
format
RS-485 1:N
3
Station No.
0 to 99
Setting item
Set value
Switch No.
1
2
3
4
5
6
7
8
disable
OFF OFF OFF
Stop bit
1bit
ON
2bits
OFF
Data bit
7bits
ON
8bits
OFF
Parity bit
Even
ON
Odd
OFF
Done
ON
None
OFF
Initializing
method
By switch
ON
ON
8
7
6
5
4
3
2
1
ON
Setting item
Set value
Switch No.
1
2
3
4
5
6
7
8
Transmission
speed
9600bps
OFF OFF OFF OFF OFF ON
OFF OFF
19200bps
OFF OFF OFF OFF OFF OFF
ON
OFF
Specification range
0 to 99
8
7
6
5
4
3
2
1
ON
GOT
Station
No.3
Station
No.0
Station
No.1
Station
No.15
Station
No.6
Examples of station number setting
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......