![Mitsubishi GOT2000Series Скачать руководство пользователя страница 166](http://html1.mh-extra.com/html/mitsubishi/got2000series/got2000series_connection-manual_1809187166.webp)
7 - 16
7. CONNECTION TO YOKOGAWA PLC
7.3 Ethernet Connection
7.3
Ethernet Connection
7.3.1
System configuration for connecting to FA-M3/M3V
*1
Product manufactured by YOKOGAWA Electric Corporation. For details of the product, contact Yokogawa Electric Corporation.
*2
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*3
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
PC link
module
FA-M3/M3V
GOT
Connection cable
Ethernet(
YOKOGAWA
), Gateway
Communication driver
PLC
Connection cable
GOT
Number of connectable
equipment
Model
name
Ethernet
interface
module
*1
Cable model
*2
Connection diagram number
Maximum
segment
length
*3
Option device
Model
F3SP05
F3SP08
F3FP36
F3SP21
F3SP25
F3SP35
F3SP28
F3SP38
F3SP53
F3SP58
F3SP59
F3SP76-7S
F3LE01-5T
F3LE11-0T
F3LE12-0T
• 10BASE-T
Shielded twisted pair cable (STP) or
unshielded twisted pair cable (UTP) :
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted pair cable (STP) :
Category 5 and 5e
100m
- (Built into GOT)
When PLC:GOT is N:1
The following shows the
number of PLCs for 1 GOT
TCP: 128 or less
UDP: 128 or less
When PLC:GOT is 1:N
The following shows the
number of GOTs for 1 PLC
TCP: 8 or less
UDP: 128 or less
(recommended to 16 or less)
F3SP66
F3SP67
F3SP71-4N
F3SP76-7S
-
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......