9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
(2) DIP switch setting (SW3)
Set the communication speed and the data bit
configuration using the DIP switch (SW3).
(3) DIP switch settings (SW4)
Set the communication specifications and the
termination resistor using the DIP switch (SW4).
9.5.18
Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
(1) Direct specification
The station number setting range of the temperature
controller side differs from that of the GOT side.
Specify the station No. of the temperature controller to
be changed when setting devices referring the following
table.
Setting item
Set value
Switch position
1
2
3
4
5
6
7
8
Communication
speed
4800bps
OFF OFF
-
9600bps
ON OFF
19200bps OFF ON
38400bps
ON
ON
Data bit
configuration
Data bit:
8 bits,
Parity:
None,
Stop: 2
bits
-
OFF OFF
-
Data bit:
8 bits,
Parity:
None,
Stop: 1 bit
-
ON OFF
-
Data bit:
8 bits,
Parity:
Even,
Stop: 1 bit
-
OFF ON
-
Data bit:
8 bits,
Parity:
Odd,
Stop: 1 bit
-
ON
ON
-
Setting item
Set value
Switch position
1
2
3
4
Communication
specification
setting
RS-422A
OFF
OFF
-
RS485
ON
ON
-
Termination
resistor setting
Enable
-
ON
Disable
-
OFF
1 2 3 4 5 6 7 8
ON
O F F O N
Dip switch(SW3)
1
O N
3
4
2
O F F
O N
Dip switch(SW4)
Temperature
controller
Module address
setting of
temperature
controller side
GOT side
station
number
setting
Remark
H-PCP-J
H-PCP-A
H-PCP-B
Z-TIO
Z-COM
0 to F
(Hexadecimal)
1 to 16
(Decimal)
The GOT side station
number setting is the module
address setting value +1.
Z-DIO
0 to F
(Hexadecimal)
17 to 32
(Decimal)
The GOT side station
number setting is the module
address setting value +17.
Z-CT
0 to F
(Hexadecimal)
33 to 48
(Decimal)
The GOT side station
number setting is the module
address setting value +33.
X-TIO
1 to 99
(Decimal)
2 to 100
(Decimal)
The GOT side station
number setting is the module
address setting value +1.
CB, FB, RB,
PF, AG, HA,
MA, RMC,
THV, SA, SB1
1 to 99
(Decimal)
1 to 99
(Decimal)
The GOT side station
number setting is the same
as the module address
setting value.
B400
1 to 99
(Decimal)
1 to 99
(Decimal)
The GOT side station
number is the module
address setting value +1 or
+2.
GOT
Station
No.10
Station
No.3
Station
No.1
Station
No.15
Station
No.6
Examples of station number setting
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......