9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.4 GOT Side Settings
9 - 39
C
O
NN
ECTION T
O
RK
C TEMPE
R
A
T
UR
E CON
T
R
O
LLER
9
9.4
GOT Side Settings
9.4.1
Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: RKC
• Controller Type: RKC SR Mini HG
• I/F: Interface to be used
• Driver: RKC SR Mini HG(MODBUS)
4.
The detailed setting is displayed after Manufacturer,
Controller Type,
I/F, and Driver are set.
Make the settings according to the usage
environment.
9.4.2Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
9.4.2
Communication detail settings
2.
3.
4.
Click!
Item
Description
Range
Transmissio
n Speed
Set this item when change the transmission
speed used for communication with the
connected equipment.
(Default: 9600bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: No)
None
Even
Odd
Retry
Set the number of retries to be performed when
a communication error occurs.
(Default: 0time)
0 to 5times
Timeout
Time
Set the time period for a communication to time
out.
(Default: 3sec)
3 to 30sec
Delay Time
Set this item to adjust the transmission timing
of the communication request from the GOT.
(Default: 0ms)
0 to 300ms
Format
Select the communication format.
(Default: 1)
Format 1:
Accessible to H-PCP-J, H-PCP-A, H-PCP-B,
SRZ, FB, PF, HA, MA, RMC, SRX, B400 series
Format 2:
Accessible to CB series, RB, AG, THV, SA, SB1
series
1/2
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......