12. CONNECTION TO LS INDUSTRIAL SYSTEMS PLC
12.3 Connection Diagram
12 - 7
CONNECTION T
O
LS INDUSTRIA
L SY
STEMS PLC
12
12.3 Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
12.3.1
RS-232 cable
Connection diagram
Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) LS INDUSTRIAL SYSTEMS PLC side connector
Use the connector compatible with the LS
INDUSTRIAL SYSTEMS PLC side module.
For details, refer to the user's manual of the LS
INDUSTRIAL SYSTEMS PLC.
12.3.2
RS-422 cable
Connection diagram
Precautions when preparing a cable
(3) Cable length
The length of the RS-422 cable must be 500m or less.
(4) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(5) LS INDUSTRIAL SYSTEMS PLC side connector
Use the connector compatible with the LS
INDUSTRIAL SYSTEMS PLC side module.
For details, refer to the user's manual of the LS
INDUSTRIAL SYSTEMS PLC.
(1) RS-232 connection diagram 1)
(2) RS-232 connection diagram 2)
1
2
3
4
5
6
7
8
9
LS INDUSTRIAL SYSTEM
PLC side
GOT side
1
7
4
2
5
3
6
8
9
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
NC
5V
TXD2
RXD2
RXD1
SG
TXD1
5V
SG
SG
1
2
3
4
5
6
7
8
9
LS INDUSTRIAL SYSTEM
PLC side
GOT side
1
3
2
4
5
6
7
8
9
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
NC
CD
TXD
RXD
DTR
SG
DSR
RTS
CTS
-
(1) RS-422 connection diagram 1)
*1
For the system terminal, connect a 120
(1/2W)
terminating resistor across RDA and RDB, and across
SDA and SDB respectively.
(2) RS422 connection diagram 3)
*1
For the system terminal, connect a 120
(1/2W)
terminating resistor across RDA and RDB, and across
SDA and SDB respectively.
GOT side
LS INDUSTRIAL SYSTEMS PLC
side (terminal block)
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
CSB
1
6
2
7
5
3
8
4
9
RDA
RDB
SDA
SDB
SG
FG
*1
RDA
RDB
SDA
SDB
SG
FG
RDA
RDB
SDA
SDB
SG
FG
LS INDUSTRIAL SYSTEMS PLC
side (terminal block)
*1
LS INDUSTRIAL SYSTEMS PLC
side (terminal block)
*1
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......