8 - 32
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.5 Temperature Controller Side Setting
8.5.6
Station number setting
Set each station number so that no station number
overlaps.
The station number can be set without regard to the cable
connection order. There is no problem even if station
numbers are not consecutive.
(1) Direct specification
When setting the device, specify the station number of
the temperature controller of which data is to be
changed.
(2) Indirect specification
When setting the device, indirectly specify the station
number of the inverter of which data is to be changed
using the 16-bit GOT internal data register (GD10 to
GD25).
When specifying the station No. from 100 to 115 on GT
Designer3, the value of GD10 to GD25 compatible to
the station No. specification will be the station No. of
the temperature controller.
(3) All station specification
Target station differs depending on write-in operation or
read-out operation.
• For write-in operation, all station will be a target.In the
WORD BIT write-in operation, only the temperature
controller whose station No. is the same as host
address is applicable.
8.4.2 Communication detail settings
• In the read-out operation, only the temperature
controller whose station No. is the same as host
address is applicable.
For details of host address setting, refer to the
following.
8.4.2 Communication detail settings
POINT
POINT
POINT
The all station specification can be set for the following
temperature controllers only.
UT420, UT450, UT520, UT550, T551, UT750,
UP550, UP750,
US1000
Specification
range
1 to 99
Specification
station NO.
Compatible
device
Setting range
100
GD10
1 to 99
For the setting other than the above,
error (dedicated device is out of
range) will occur.
101
GD11
102
GD12
103
GD13
104
GD14
105
GD15
106
GD16
107
GD17
108
GD18
109
GD19
110
GD20
111
GD21
112
GD22
113
GD23
114
GD24
115
GD25
GOT
Station
No.3
Station
No.7
Station
No.1
Station
No.15
Station
No.6
Examples of station number setting
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......