7. CONNECTION TO YOKOGAWA PLC
7.3 Ethernet Connection
7 - 21
7
CONN
ECTION
T
O
YOKOGA
W
A
PLC
7.3.6
Connecting to F3SP66,
F3SP67, F3SP71-4N (built-in
Ethernet interface)
Project setting/configuration setting
Set the setting with software for programming
apparatus.
*1
Adjust the settings with GOT settings.
■
*2
For the port No. of the GOT, set the port No. of the host link
service to be used.
■
*3
Set this as necessary.
7.3.7
Precautions
Device range
When performing monitoring with the GOT connected
to a YOKOGAWA PLC and setting devices for objects,
use devices within the device range of the
YOKOGAWA PLC.
When a device outside the range is set on an object, an
indefinite value is displayed on the object.
(No error is displayed in the system alarm.)
For details on the device range of YOKOGAWA PLCs,
refer to the following manual:
7.4 Device Range that Can Be Set
When setting IP address
Do not use "0" and "255" at the end of an IP address.
(Numbers of *.*.*.0 and *.*.*.255 are used by the
system.)
The GOT may not monitor the controller correctly with
the above numbers.
Consult with the administrator of the network before
setting an IP address to the GOT and controller.
When connecting to multiple GOTs
(1) Setting Station
When connecting two or more GOTs in the Ethernet
network, set each [Station] to the GOT.
■
(2) Setting IP address
Do not use the IP address "192.168.0.18" when using
multiple GOTs.
A communication error may occur on the GOT with the
IP address.
When connecting to the multiple network
equipment (including GOT) in a segment
By increasing the network load, the transmission speed
between the GOT and PLC may be reduced.
The following actions may improve the communication
performance.
• Using a switching hub
• More high speed by 100BASE-TX (100Mbps)
• Reduction of the monitoring points on GOT
Item
Set value
Description
IP address
*1
0.0.0.0 to
255.255.255.255
Set the IP address of the
connected Ethernet module.
Host link service A
protocol
*2
Port No.: 12289
0=TCP/IP
*1
1=UDP/IP
*1
Select the protocol to be used
in the port A of the host link
service via Ethernet.
Host link service A
protocol command
data type
*2
Port No.: 12289
0=ASCII format
Select the command data type
to be used in the port A of the
host link service via Ethernet.
Host link service B
protocol
*2
Port No.: 12291
0=TCP/IP
*1
1=UDP/IP
*1
Select the protocol to be used
in the port B of the host link
service via Ethernet.
Host link service B
protocol command
data type
*2
Port No.: 12291
0=ASCII format
Select the command data type
to be used in the port B of the
host link service via Ethernet.
Write protection
*3
0 = Not protected
1 = Protected
Disables the write command to
this module with the host link
service via Ethernet.
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......