APPX
Appendix 3 Buffer Memory
81
A
■
Alarm history areas (Un\G256 to Un\G511)
Address
(decimal)
Address
(hexadecimal)
Name
Default
value
Data type
Auto
refresh
256
100H
Latest address of alarm history
0
Monitor
257 to 271
101H to 10FH
System area
272
110H
Alarm history No.1
Alarm code
0
Monitor
273
111H
Alarm time
First two
digits of the
year
Last two
digits of the
year
274
112H
Month
Day
275
113H
Hour
Minute
276
114H
Second
Day of the
week
277
115H
Millisecond
278, 279
116H, 117H
System area
280 to 285
118H to 11DH
Alarm history No.2
Same as Alarm history No.1
0
Monitor
286, 287
11EH, 11FH
System area
288 to 293
120H to 125H
Alarm history No.3
Same as Alarm history No.1
0
Monitor
294, 295
126H, 127H
System area
296 to 301
128H to 12DH
Alarm history No.4
Same as Alarm history No.1
0
Monitor
302, 303
12EH, 12FH
System area
304 to 309
130H to 135H
Alarm history No.5
Same as Alarm history No.1
0
Monitor
310, 311
136H, 137H
System area
312 to 317
138H to 13DH
Alarm history No.6
Same as Alarm history No.1
0
Monitor
318, 319
13EH, 13FH
System area
320 to 325
140H to 145H
Alarm history No.7
Same as Alarm history No.1
0
Monitor
326, 327
146H, 147H
System area
328 to 333
148H to 14DH
Alarm history No.8
Same as Alarm history No.1
0
Monitor
334, 335
14EH, 14FH
System area
336 to 341
150H to 155H
Alarm history No.9
Same as Alarm history No.1
0
Monitor
342, 343
156H, 157H
System area
344 to 349
158H to 15DH
Alarm history
No.10
Same as Alarm history No.1
0
Monitor
350, 351
15EH, 15FH
System area
352 to 357
160H to 165H
Alarm history
No.11
Same as Alarm history No.1
0
Monitor
358, 359
166H, 167H
System area
360 to 365
168H to 16DH
Alarm history
No.12
Same as Alarm history No.1
0
Monitor
366, 367
16EH, 16FH
System area
368 to 373
170H to 175H
Alarm history
No.13
Same as Alarm history No.1
0
Monitor
374, 375
176H, 177H
System area
376 to 381
178H to 17DH
Alarm history
No.14
Same as Alarm history No.1
0
Monitor
382, 383
17EH, 17FH
System area
384 to 389
180H to 185H
Alarm history
No.15
Same as Alarm history No.1
0
Monitor
390, 391
186H, 187H
System area
392 to 397
188H to 18DH
Alarm history
No.16
Same as Alarm history No.1
0
Monitor
398 to 511
18EH to 1FFH
System area