APPX
Appendix 3 Buffer Memory
103
A
Output delay time setting
Set the output delay time for each output.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Setting range
• The available range is 1 to 150000 (400
s to 60s). (Set the range in increments of 400
s.)
• The output delay time setting error (error code: 1A4
H) occurs in the output terminal where a value out of the setting range
has been set.
indicates the number of an I/O terminal in which the error has occurred. (
= 0H to FH)
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 (400
s) for all the inputs.
Number of output ON times integration function enable/disable
Set whether to enable or disable the number of output ON times integration function for each output.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (Disable) for all the outputs.
Buffer memory name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
Output delay time setting
1840
1841
1842
1843
1844
1845
1846
1847
1848
1849
1850
1851
1852
1853
1854
1855
1856
1857
1858
1859
1860
1861
1862
1863
1864
1865
1866
1867
1868
1869
1870
1871
(1) 0: Disable, 1: Enable
Buffer memory name
Y0 to YF
Number of output ON times integration function
enable/disable
1904
Y00
(1)
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......