8 SYSTEM CONFIGURATION
8.2 Redundant Line
• List of components
No.
Name
Description
(1)
System A system
Composed of the following modules:
• RnPSFCPU
• R6PSFM
• R6RFM
• RJ71GF11-T2
■
Precautions
• Each module has restrictions on use in a system on the system configuration diagram. For details,
refer to the User's Manual (Application) for each module.
• Mount the above modules on the same base unit. Mount the modules so that they are arranged in
the following order: RnPSFCPU
R6PSFM
R6RFM
RJ71GF11-T2, starting from the right
side of the power supply module.
(2)
System B system
Composed of the following modules:
• RnPSFCPU
• R6PSFM
• R6RFM
• RJ71GF11-T2
■
Precautions
• Each module has restrictions on use in a system on the system configuration diagram. For details,
refer to the User's Manual (Application) for each module.
• Mount the above modules on the same base unit. Mount the modules so that they are arranged in
the following order: RnPSFCPU
R6PSFM
R6RFM
RJ71GF11-T2, starting from the right
side of the power supply module.
(3)
Tracking cable
Use cables designed for use by the R6RFM. (
MELSEC iQ-R CPU Module User's Manual
(Startup))
(4)
CC-Link IE Field Network supporting cable
Use cables supporting CC-Link IE Field Network. (
MELSEC iQ-R Ethernet/CC-Link IE User's
Manual (Startup))
(5)
Remote head module
Use two sets of the RJ72GF15-T2 to build a redundant configuration. Note that the module has
restrictions on use in a system on the system configuration diagram. For details, refer to the
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application).
(6)
RX40NC6B SIL2 mode set
Composed of the following modules:
• RX40NC6B(Main)
• RX40NC6B(Sub)
■
Precautions
• When using the RX40NC6B in SIL2 mode, there is a restriction on the version. For details, refer to
Page 141 Firmware Version for SIL2 Mode.
• Mount the above modules on the same base unit. Mount the modules so that they are arranged in
the following order: RX40NC6B(Main)
RX40NC6B(Sub), starting from the right side of the
remote head module.
(7)
RY40PT5B SIL2 mode set
Composed of the following modules:
• RY40PT5B(Main)
• RY40PT5B(Sub)
■
Precautions
• When using the RY40PT5B in SIL2 mode, there is a restriction on the version. For details, refer to
Page 141 Firmware Version for SIL2 Mode.
• Mount the above modules on the same base unit. Mount the modules so that they are arranged in
the following order: RY40PT5B(Main)
RY40PT5B(Sub), starting from the right side of the
remote head module.
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......