1 FUNCTIONS
1.3 Common Functions of the I/O Module with Diagnostic Functions
41
1
Setting example
Ex.
To execute an interrupt program when a disconnection is detected at X0 of the input module with diagnostic functions
• Parameter setting
Set "Interrupt setting" of the module parameters as shown below.
• Label setting
No.
Interrupt condition target setting Interrupt condition target input
output terminal setting range
Interrupt pointer
1
Disconnection detection state
X00
I50
Classification
Label name
Description
Device
Module label
RCPU.stSM.bAlways_ON
Always ON
SM400
RCPU.stSM.bAfter_RUN1_Scan_ON
ON only for a scan after RUN
SM402
RX40NC6B_1.unInterruptFactorMask_D[0]
Interrupt factor mask [1]
U0\G3344
RX40NC6B_1.unInterruptFactorResetRequest_D[0]
Interrupt factor reset request [1]
U0\G3328
Defined labels
Define global labels as shown below.
(0)
(62)
Only the interrupt pointer I50 can be executed.
'Interrupt factor reset request [1]' (U0\G3328) is turned on.
The processing at disconnection detection is performed.