10 FUNCTIONS
10.1 SIL2 Mode
157
10
7.
Click the [Enable] button. In this case, the current enabled/disabled status of the safety module is displayed for "Module
Status".
8.
Check that "Valid (Reset Wait)" is displayed for "Module Status". The enabling or disabling operation can be reflected in
the I/O module with diagnostic functions by resetting the remote head module or turning off and on the power.
9.
Reset the remote head module or turn off and on the power, and click the [Update] button.
10.
Check that "Valid" is displayed for "Module Status".
• If a module that is already enabled is attempted to be enabled, the status does not change to "Valid (Reset
Wait)" while the status is in "Valid".
• When changing a module parameter of the I/O module with diagnostic functions, enabling the safety
module is required again.
Module Status
Description
The information is not acquired.
Valid (Reset Wait)
The safety module has just been enabled. In this state, the I/O module with diagnostic functions needs to be reset,
and the module status will be enabled after the reset. At this time, the ALM LED flashes every 0.4 seconds.
Verification Failed
The module parameters are different between the SIL2 Process CPU project and the remote head module project.
Ensure that the module parameters are consistent.
Enabling Failed (Module Error)
The safety module failed to be enabled. Check wiring or other items and retry it. If this error persists, the module may
be in failure.
Enabling Failed (Data Error)
Timeout
A timeout occurred because no response was returned from the target module. Check the settings or status of the
target module.
• Is the module is set to SIL2 mode?
• Has an error occurred?