APPX
Appendix 3 Buffer Memory
107
A
Output disconnection detection disable time setting
Set an output disconnection detection disable time for each module.
When a numerical value other than the above is set, the set value is regarded as 1 (100ms).
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 (100ms).
Latest error code
The latest error code detected in the I/O module with diagnostic functions is stored. For details, refer to the following.
Page 68 List of Error Codes
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
How to clear an error
Turn on and off 'Error clear request' (Y10).
Latest alarm code
The latest alarm code detected in the I/O module with diagnostic functions is stored. For details, refer to the following.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
How to clear an alarm
Turn on and off 'Alarm clear request' (Y11).
Setting value
Description
0
0ms
1
100ms
2
200ms
3
300ms
Buffer memory name
Y0 to YF
Output disconnection detection disable time
setting
1988
Buffer memory name
X/Y0 to X/YF
Latest error code
2560
Buffer memory name
X/Y0 to X/YF
Latest alarm code
2564
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......