13 TROUBLESHOOTING
13.2 Checking the Module Status
Module Information List
Status information of the I/O module with diagnostic functions can be checked by selecting the "Module Information List" tab.
If a minor error occurs when "LED display settings during an error" of "Basic setting" is set to "Display I/O
status and error switching (1 second interval)", "On" and "Off" are alternatively displayed for "ALM" of "LED
information". (The duration of display may differ between "On" and "Off", because "ALM" area reflects the
status of the I/O module with diagnostic functions during communications with the I/O module.) In addition,
"On" and "Off" are output in CSV format by clicking "Create File".
For this reason, when checking LED status on the "Module Diagnostics" window, do not set "LED display
settings during an error" of "Basic setting" to "Display I/O status and error switching (1 second interval)".
Item
Description
LED information
Displays the status of each LED of the I/O module with diagnostic functions.
External input monitor signal X00 to X0F (SIL2 mode MAIN)
External input monitor signal X00 to X0F (SIL2 mode Sub)
Displays the status of external input for each input.
Redundant input discrepancy detection state
Displays the double input discrepancy detection state for each input.
Auto recovery settings after discrepancy error
Displays the setting status of double input discrepancy auto recovery setting.