3 TROUBLESHOOTING
3.4 List of Error Codes
69
3
1B00H
LED indication setting on error
condition error
A value other than 0 to 2 has been set in LED
indication setting on error condition.
Set a value of 0 to 2 in LED indication setting on
error condition.
For details on LED indication setting on error
condition, refer to the following.
Page 92 LED indication setting on error
1EA0H
Synchronization cycle setting too
short error
A value of 0.20ms or less has been set in "Fixed
Scan Interval Setting of Inter-module
Synchronization", which is a system parameter.
Set a value of 0.222ms or more in "Fixed Scan
Interval Setting of Inter-module Synchronization",
which is a system parameter.
3001H
Hardware error
A hardware error has been detected.
The possible cause is noise or a hardware failure.
If measures to reduce noise do not eliminate this
error, the possible cause is a failure of the module.
Please consult your local Mitsubishi
representative.
3040H
Start-up in normal mode with
safety validated
The module whose function as the safety
module was enabled was started up in normal
mode.
To use the module in normal mode, disable the
safety module function. For the procedure how to
disable the safety module function, refer to the
following.
Page 118 Disabling the Safety Module
Error code
Error name
Error description and cause
Action
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......