184
10 FUNCTIONS
10.9 Event History Function
Event history list
The following table shows an event that occurs in the I/O module with diagnostic functions.
*1 Although this event may occur on the switching of systems incorporating SIL2 Process CPUs, an input value or output value is held
within a period where the input HOLD function or output HOLD function is effective (the time set with "Safety I/O Hold Time" in "CPU
Parameter").
Event
code
Event
classification
Event name
Description
Additional
information
00150
Information
Safety communication start
Safety communications were started.
00151
Information
Safety communication stop
Safety communications were stopped.
00A00
Alarm
Safety communication error
A safety communication error was detected.
00A02
Alarm
Response monitoring timeout with safety
communication connection being
established
A response timeout occurred while a safety communication
connection was being established.
00A03
Alarm
Response monitoring timeout during safety
communication refresh
A response timeout occurred during safety communication
refresh.
00A04
Alarm
Response monitoring timeout during safety
communication error processing
A timeout occurred during the safety communication error
response.
00A05
Alarm
Safety communication reception interval
monitoring timeout
No response was returned within the specified safety refresh
monitoring time.
00A06
Alarm
Safety communication receive data delay
detection
Consecutive receive data is not complete.
00A07
Alarm
Safety communication receive data loss
detection
A loss of consecutive receive data was detected.
00A08
Alarm
Application data error
A safety communication data frame error was detected.
00A10
Alarm
Safety module validation match failure
An error was detected at the verification of safety parameter.
00A11
Alarm
Failure of enabling safety module
Enabling the safety parameter failed.
00A12
Alarm
Failure of disabling safety module
Disabling the safety parameter failed.
20100
Information
Error release (error clear)
An error clear request was executed.
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Страница 227: ......