76
APPX
Appendix 2 I/O Signals
Alarm flag
'Alarm flag' (X11) turns on when an alarm occurs.
■
Device number
The following table shows the device number of this input signal.
Operating condition setting completed flag
This signal is used as an interlock condition to turn on and off 'Operating condition setting request' (Y12) when the value of a
buffer memory area is changed.
For the buffer memory areas that require 'Operating condition setting request' (Y12) to be turned on and off to enable new
values, refer to the following.
Page 79 List of buffer memory addresses
■
Device number
The following table shows the device number of this input signal.
Module READY
This signal is used as an interlock condition to read/write data from/to the CPU module.
When the initial processing of the I/O module with diagnostic functions is completed after the CPU module is powered on or is
reset, Module READY turns off.
When a watchdog timer error occurs, Module READY turns on.
■
Device number
The following table shows the device number of this input signal.
: Performed by the I/O module with diagnostic functions.
: Performed by a program.
Signal name
External input/output
X/Y00 to X/Y0F
Alarm flag
X11
: Performed by the I/O module with diagnostic functions.
: Performed by a program.
Signal name
External input/output
X/Y00 to X/Y0F
Operating condition setting completed flag
X12
Signal name
External input/output
X/Y00 to X/Y0F
Module READY
X1F
OFF
OFF
ON
0
0
ON
Alarm code
'Latest alarm code'
(Un\G2564)
'Alarm flag'
(X11)
'Alarm clear request'
(Y11)
OFF
OFF
ON
ON
ON
'Operating condition setting
completed flag' (X12)
'Operating condition setting
request' (Y12)