9 INSTALLATION AND WIRING
9.3 Wiring Examples
Safety (door) switch wiring
With two input modules with diagnostic functions, a safety (door) switch is wired as follows:
■
Input double wiring
Apply input double wiring in either of the following combinations.
• For the RX40NC6B (Main) and the RX40NC6B (Sub), wire even-numbered input terminals with T0 test pulse output
terminals.
• For the RX40NC6B (Main) and the RX40NC6B (Sub), wire odd-numbered input terminals with T1 test pulse output
terminals.
(1) This is a door switch with two normally closed contacts based on direct opening action. Connect this door switch between X00 to X0F (input) terminals and
T0 (test pulse output) terminals.
(2) This is a spring lock type door switch with two normally closed contacts based on direct opening action. Connect this door switch between X00 to X0F (input)
terminals and T1 (test pulse output) terminals and 24VDC terminals.
RX40NC6B(Main)
RX40NC6B(Sub)
Input terminal
Test pulse output terminal
Input terminal
Test pulse output terminal
X00
T0
X00
T0
X01
T1
X01
T1
to
to
X0E
T0
X0E
T0
X0F
T1
X0F
T1
X01
(1)
(2)
X03
X05
X07
X09
X0B
X0D
X0F
COM
X00
RX40NC6B(Main)
RX40NC6B(Sub)
X02
X04
X06
X08
X0A
X0C
X0E
DC24V
T1
T0
X01
X03
X05
X07
X09
X0B
X0D
X0F
COM
X00
X02
X04
X06
X08
X0A
X0C
X0E
DC24V
T1
T0
Open
Open
24VDC