[2-7 Example System with an MA Remote Controller ]
BS_02_L
20
-
chapter 2
2
Rest
rict
io
ns
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block for indoor-
outdoor transmission line (TB3) on the outdoor unit (OC), of the ter-
minal block for indoor-outdoor transmission line (TB3) on the main
and sub HBCs (HB and HS), of the terminal block for indoor-outdoor
transmission line (TB5) on each indoor unit (IC), and the S terminal
of the system controller.(Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Daisy-chain the ground terminal (
) on the outdoor unit (OC), the
S terminal of the terminal block (TB3) on the HB and HS, and the S
terminal of the terminal block (TB5) on the indoor unit (IC) with the
shield of the shielded cable.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block for transmis-
sion line for centralized control (TB7) on the outdoor units (OC) in
different refrigerant circuit and on the OC in the same refrigerant cir-
cuit.
If a power supply unit is not connected to the transmission line for
centralized control, replace the power jumper connector on the con-
trol board from CN41 to CN40 on only one of the outdoor units.
Set the central control switch (SW5-1) on the control board of all out-
door units to "ON."
a) When connecting TB7, only commence after checking that the volt-
age is below 20 VDC.
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the out-
door units (OC, OS) with the shield wire of the shielded cable. Short-
circuit the earth terminal (
) and the S terminal on the terminal
block (TB7) on the outdoor unit whose power jumper connector is
mated with CN40.
3) MA remote controller wiring
Same as 2-7-1
When 2 remote controllers are connected to the system
Same as 2-7-1
Group operation of indoor units
Same as 2-7-1
4) Switch setting
Address setting is required as follows.
(5) Address setting method
Proce-
dures
Unit or controller
Address
setting
range
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit
IC
01 to
50
Assign the smallest address to the main unit
in the group.
In a system with two or more HBCs, make
the settings for the indoor units in the fol-
lowing order.
(i) Indoor unit to be connected to the main
HBC
(ii) Indoor unit to be connected to the sub
HBC 1
(iii) Indoor unit to be connected to the sub
HBC 2
(iv) Indoor unit to be connected to the sub
HBC 3
Make the settings for the indoor units in the
way that the formula "(i) < (ii) < (iii)< (iv)" is
true.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
00
Sub unit
Assign sequential numbers starting with the
address of the main unit in the same group
+1. (Main unit a1, main unit address
+2, main unit a3, etc.)
2
MA
remote
controller
Main
remote con-
troller
MA
No set-
tings re-
quired.
-
Make the same indoor unit
group settings with the system
controller as the ones that
were made with the MA remote
controller.
Main
Sub
remote con-
troller
MA
Sub
remote
controller
Settings to be made with the Sub/
Main switch
3
Outdoor unit
OC
51 to 100
Set the address to "the smallest indoor unit
address in the same refrigerant circuit sys-
tem + 50."
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main HBC
overlaps any of the address-
es that are assigned to the
outdoor units or to the sub
HBC, use a different, un-
used address within the set-
ting range.
The use of a sub HBC re-
quires the connection of a
main HBC.
00
4
Auxiliary
outdoor
unit
HBC (Main)
HB
51 to 100
OC +1
HBC (Sub)
HS
Assign an address that equals the sum of the
smallest address of the indoor units that are
connected to the sub HBC and 50.
0000006407.BOOK 20 ページ 2021年10月12日 火曜日 午後4時22分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......