[2-7 Example System with an MA Remote Controller ]
BS_02_L
chapter 2 -
17
2
Rest
rict
io
ns
2-7-4
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
An example of a system in which a system controller is connected to the transmission cable for the centralized control system
and the power is supplied from the outdoor unit
(2) Cautions
1) ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group
of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units (not required if power to the
transmission line for centralized control is supplied from a controller
with a power supply function, such as GB-50ADA).
5) Short-circuit the shield terminal (S terminal) and the earth terminal (
) on the terminal block for transmission line for centralized control
(TB7) on the outdoor unit whose power jumper connector is mated
with CN40.
6) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
The left table shows the number of transmission boosters that is re-
quired by the system with four HBCs. For each HBC added or sub-
tracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how many
booster units are required for a given system.
7) When a power supply unit is connected to the transmission line for
centralized control, leave the power jumper connector on CN41 as it
is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
L31+L32 200m
[656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L32+L31+L12
1000 m [3280ft] (500 m [1640ft])
*1
L32+L22
1000 m [3280ft] (500 m [1640ft])
*1
L12+L31+L22
1000 m [3280ft] (500 m [1640ft])
*1
*1 If a given system includes one or more unit or remote controller
that does not support the maximum allowable cable distance of
1000 m [3280 ft], the maximum allowable cable distance in the
system will be 500 m [1640 ft]. Refer to the latest catalog for in-
formation on which units and remote controllers support the max-
imum allowable cable distance of 1000 m [3280 ft].
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
A
1
B
2
MA
A
1
B
2
MA
LC
TB5
S
07
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
05
04
LC
TB5
S
08
IC
TB5
S
TB15
1 2
03
A
1
B
2
MA
IC
TB5
S
TB15
1 2
06
A
1
B
2
MA
A
1
B
2
MA
m3
L31
System controller
A B S
Note1
L32
OC
To be connected
m2
m1
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220 - 240V.
TB3
TB7
S
51
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
OC
TB3
TB7
S
54
Group
Group
Group
Group
Group
Interlock operation with
the ventilation unit
Move the male connector
from CN41 to CN40.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
To be left
unconnected
S
HB
TB3
52
S
HB
TB3
55
L22
L12
Number of transmission booster
(sold separately) required
1 unit
2 units
When the W/WP/WL200 and
W/WP/WL250 models are not includ-
ed in the connected indoor units
25 - 50 units
-
When the W/WP/WL200 and
W/WP/WL250 models are included in
the connected indoor units
19 - 37 units
38 - 50 units
0000006407.BOOK 17 ページ 2021年10月12日 火曜日 午後4時22分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......