[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
62
-
chapter 7
BS_07_M
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-8-3
Error Code [6600]
1. Error code definition
Address overlaps
2. Error definition and error detection method
An error in which signals from more than one indoor units with the same address are received
Detail code 001: Detection of overlapped address in centralized control system
Detail code 002: Detection of overlapped address in indoor unit system
The address and attribute that appear on the remote controller indicate the controller that detected the error.
3. Cause, check method and remedy
7-8-4
Error Code [6601]
1. Error code definition
Polarity setting error
2. Error definition and error detection method
The error detected when transmission processor cannot distinguish the polarities of the M-NET transmission line.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Two or more of the following have the same address:
Outdoor units, HBCs, indoor units, LOSSNAY units,
controllers such as ME remote controllers.
<Example>
6600 "01" appears on the remote controller
Unit #01 detected the error.
Two or more units in the system have 01 as their ad-
dress.
Find the unit that has the same address as that of the error
source.
Once the unit is found, correct the address. Then, turn
off the outdoor units, indoor units, HBCs, and
LOSSNAY units, keep them all turned off for at least
five minutes, and turn them back on.
When air conditioning units are operating normally despite
the address overlap error
Check the transmission wave shape and noise on the
transmission line.
Refer to the following page(s). [8-4 Checking Transmission
Waveform and for Electrical Noise Interference]
(2)
Signals are distorted by the noise on the transmission
line.
Cause
Check method and remedy
(1)
No voltage is applied to the M-NET transmission line
that AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150 are connected to.
Check if power is supplied to the M-NET transmission
line of the AE-200E/AG-150A/GB-50ADA/PAC-
YG50ECA/BAC-HD150, and correct any problem found.
(2)
M-NET transmission line to which AE-200/AG-150A/
GB-50ADA/PAC-YG50ECA/BAC-HD150 are con-
nected is short-circuited.
(3)
When two or more power supplies are connected to
the M-NET
0000006452.BOOK 62 ページ 2021年10月27日 水曜日 午前9時38分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......