[8-9 Troubleshooting Problems with Major Components on HBC ]
34
-
chapter 8
BS_08_L
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-9
Troubleshooting Problems with Major Components on HBC
8-9-1
Pressure Sensor
Troubleshooting flow chart for pressure sensor
Check the connectors on pressure
sensor PS1, PS3, Pw1, Pw2, Pw3,
Pw4 for proper connections.
All the compressors of the outdoor units to
which the HBC is connected are stopped.
All the pumps of HBC are stopped.
Check PS1, PS3, Pw1, Pw2, Pw3, Pw4 on the
self-diagnosis LED, and check that the pressure
reading is 0.098 MPa [14 psi] or above.
On the self-diagnosis monitor, measure
• Outdoor high-pressure 63HS1
• Outdoor low-pressure 63LS
• HBC pressure PS1, PS3 (refrigerant side)
• HBC pressure Pw1, Pw2, Pw3, Pw4 (water side)
Check whether the result is
63HS1 > PS1, PS3 > 63LS
Pw1, Pw3 > 0.01MPa
Pw2, Pw4 > Supply-water pressure
START
Repair the fault.
Fix the relation between
the refrigerant piping
and the transmission line.
Fix the relation between the
refrigerant piping and the
transmission line.
Replace the pressure sensor.
Replace the board.
Restore contact failure.
Check whether the contact of the pressure
sensor connector in trouble is not faulty.
OK?
OK?
Check that the difference between each
detected pressure is 0.098MPa [14psi] or less.
OK?
Both the board and the pressure sensor are normal.
OK?
Is Pd > PS1, PS3 > Ps?
,V3Z3Z3Z3Z
6XSSO\ZDWHUSUHVVXUH"
Remove the pressure sensor connector
from the board, and check the pressure.
OK?
OK?
Check whether the refrigerant pipe and the
transmission line are connected correctly
between the outdoor unit and the HBC, the
indoor unit and the HBC.
OK?
Operating at the moment?
Check whether the refrigerant pipe / water
pipe and the transmission line are connected
correctly between the outdoor unit and the
HBC, the indoor unit and the HBC.
OK?
YES
Note 1
NO
YES
YES
YES
Note 2
Note 3
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
NO
NO
YES
NO
YES
NO
NO
Replace the pressure sensor, which detects
less than 6MPa [870psi] pressure, with the
pressure sensor, which detects 6MPa [870psi]
or more pressure, check the pressure, and
check whether the detected pressure is
displayed normally.
Short-circuit between connecter pins #2 and #3
on the circuit board, and check the pressure.
10 minutes or longer after
the operation stops?
Pressure 0MPa [0psi]
6MPa [870psi] pressure
or more is displayed.
0000006416.BOOK 34 ページ 2021年10月26日 火曜日 午後5時30分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......