7-7-10
Error Code [5211-5214]
1. Error code definition
5211
Pump 1 suction pressure fault (HBC Pw1)
5212
Pump 1 discharge pressure fault (HBC Pw2)
5213
Pump 2 suction pressure fault (HBC Pw3)
5214
Pump 2 discharge pressure fault (HBC Pw4)
2. Error definition and error detection method
1) If a short-circuit (high-pressure intake) or an open-circuit (low-pressure intake) of the pressure sensor Pw1 or Pw2 is de-
tected while Pump 1 is in operation, the unit will come to an abnormal stop, and the error code 5211 or 5212 will appear.
2) If a short-circuit (high-pressure intake) or an open-circuit (low-pressure intake) of the pressure sensor Pw3 or Pw4 is de-
tected while Pump 2 is in operation, the unit will come to an abnormal stop, and the error code 5213 or 5214 will appear.
3. Cause, check method and remedy
7-7-11
Error Code [5301] Detail Code 115
1. Error code definition
ACCT sensor fault (Detail code 115)
2. Error definition and error detection method
When the formula "output current < 1.8 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Pressure sensor fault
Refer to [8-9-1 Pressure Sensor].
(2)
Broken wire coating
Check for broken wire coating.
(3)
Missing connector pins, contact failure
Check for missing connector pins.
(4)
Disconnected wire
Check for disconnected or broken wire.
Cause
Check method and remedy
(1)
Contact failure
Check the connector (CNCT2) on the INV board for proper connection.
(2)
INV output phase loss
Check the output wire for proper connection.
(3)
ACCT sensor failure
Refer to the following page(s).
[8-10-18 Simple Check on Inverter Circuit Components]
(4)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems]
(5)
INV board failure
Replace the INV board if the problem persists after the operation is resumed.
0000006452.BOOK 55 ページ 2021年10月27日 水曜日 午前9時38分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......