[2-7 Example System with an MA Remote Controller ]
BS_02_L
14
-
chapter 2
2
Rest
rict
io
ns
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
unit (OC), of the terminal block for indoor-outdoor trans-
mission line (TB3) on the main and sub HBCs (HB and
HS), and of the terminal block for indoor-outdoor trans-
mission line (TB5) on each indoor unit (IC). (Non-polar-
ized two-wire)
Only use shielded cables.
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor unit
(OC), the S terminal of the terminal block (TB3) on HB
and HS, and the S terminal of the terminal block (TB5) on
the indoor unit (IC) with the shield of the shielded cable.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Same as 2-7-1
When 2 remote controllers are connected to the sys-
tem
Same as 2-7-1
Group operation of indoor units
Same as 2-7-1
4) Switch setting
Address setting is required as follows.
(5) Address setting method
Proce-
dures
Unit or controller
Address
setting
range
Setting method
Notes
Fac-
tory
set-
ting
1
Indoor
unit
Main unit
IC
01 to 50
Assign the smallest address to the main
unit in the group.
In a system with two or more HBCs make
the settings for the indoor units in the fol-
lowing order.
(i) Indoor unit to be connected to the main
HBC
(ii) Indoor unit to be connected to the sub
HBC 1
(iii) Indoor unit to be connected to the sub
HBC 2
(iv) Indoor unit to be connected to the sub
HBC 3
Make the settings for the indoor units in
the way that the formula "(i) < (ii) < (iii) <
(iv)" is true.
Port number setting is
required
To perform a group op-
eration of indoor units
that feature different
functions, designate
the indoor unit in the
group with the greatest
number of functions as
the main unit.
00
Sub unit
Assign sequential numbers starting with
the address of the main unit in the same
group +1. (Main unit a1, main unit
a2, main unit a3, etc.)
2
MA
remote
controller
Main
remote
controller
MA
No set-
tings re-
quired.
-
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made with the Sub/
Main switch
3
Outdoor unit
OC
51 to 100
Set the address to "the smallest indoor
unit address in the same refrigerant cir-
cuit 50."
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main HBC
overlaps any of the address-
es that are assigned to the
outdoor units or to the sub
HBC, use a different, un-
used address within the set-
ting range.
The use of a sub HBC re-
quires the connection of a
main HBC.
00
4
Auxiliary
outdoor
unit
HBC
(Main)
HB
51 to 100 OC +1
HBC
(Sub)
HS
Assign an address that equals the sum of
the smallest address of the indoor units
that are connected to the sub HBC and 50.
0000006407.BOOK 14 ページ 2021年10月12日 火曜日 午後4時22分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......