[5-2 Outdoor Unit Control ]
14
-
chapter 5
BS_05_M
5
Cont
rol
5-2-6
Defrost Operation Control
(1) Starting the defrost operation
The defrost cycle will start when all of the three conditions (outside temperature, cumulative compressor operation time, and
pipe temperature) under <Condition 1>, <Condition 2>, or <Condition 3> are met.
1) Pipe temperature(TH3)
The defrost cycle will not start until a minimum of 10 minutes have passed since the completion of the last defrost cycle.
If 10 minutes have passed since compressor startup or since the completion of a defrost cycle, a forced defrost cycle can be
started by setting DIP SW4 (913) to ON.
Even if the defrost-prohibit timer is set to 90 minutes, the actual defrost-prohibit time for the next defrost cycle is 50 minutes
if the last defrost cycle took 12 minutes.
Condition 1
Condition 2
Condition 3
Outside temperature
(TH7)
-5ºC [23ºF] or above
-5ºC [23ºF] or below
Cumulative compressor
operation time
50 minutes or more
90 minutes or more if the defrost prohibit timer is set to 90.
250 minutes or more
Pipe temperature
(TH3)
The pipe temperature has
stayed below the temperatures
in the table below (Note1) for
three minutes.
((E)M200-(E)M500)
The pipe temperature has
stayed below the value ob-
tained from the formula "Out-
side temperature (TH7) - 5ºC
[23ºF] " for three minutes, or the
63LS reading has stayed below
the value obtained from the for-
mula "1.5 + 0.02 x (20+TH7)"
for three minutes.
The pipe temperature has
stayed below the temperatures
in the table below (Note1) for
three minutes
M200
M250
M300
M350
M400
M450
M500
SW4 (915) OFF
-8ºC
-8ºC
-8ºC
-10ºC
-10ºC
-8ºC
-8ºC
SW4 (915) ON
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
EM200
EM250
EM300
EM350
EM400
EM450
EM500
SW4 (915) OFF
-8ºC
-8ºC
-8ºC
-10ºC
-10ºC
-8ºC
-8ºC
SW4 (915) ON
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
-5ºC
0000006450.BOOK 14 ページ 2021年10月26日 火曜日 午後7時2分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......