[5-1 Dipswitch Functions and Factory Settings ]
6
-
chapter 5
BS_05_M
5
Cont
rol
5-1-2
Indoor Unit Switch Functions and Factory Settings
(1) Dipswitches
1) SW1,3
Note 2. If both SW1-7 and SW1-8 are set to ON, the fan remains stopped during heating Thermo-OFF.
To prevent incorrect temperature detection due to a build-up of warm air around the indoor unit, use the built-in temperature sensor on the remote controller (SW1-1)
instead of the one on the indoor unit inlet thermistor.
Switch
Function
Function according to switch setting
OFF
ON
Switch setting timing
Notes
SW1
SW3
1
2
3
4
5
6
7
8
9
10
9
10
1
2
3
4
5
6
7
8
Room temperature
detection position
Clogged filter detection
Filter check reminder time setting
Outside air intake
Remote display option
Humidifier control
Self-recovery after power failure
Fan speed setting for
Heating Thermo-OFF
Power source start-stop
Unit model selection
Louver
Vane
Vane swing function
Vane horizontal angle *
1
Vane horizontal angle *
1
First setting*
2
Second setting*
2
Setting i-See sensor
installation position
Heating 4°C [7.2°F] up
Indoor unit inlet
100h
Disabled
Fan output
2500h
Enabled
Thermo-ON signal
Built-in sensor on
the remote controller
Available
During heating operation
According to the
SW1-7 setting
Heat pump
Always on while in the heating mode
Fan speed setting for
Heating Thermo-OFF
Very Low
Low
Preset speed
Cooling only
Enabled
Depends on SW3-5
Third setting*
2
Disabled
Disabled
Enabled
Enabled
Not available
Setting pattern *
1
Setting pattern *
1
Available
Not available
Available
Not available
Not available
Available
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
While the unit is stopped
(Remote controller OFF)
PLFY-WP-VBM model only
PLFY-WP-VBM model only
PLFY-WP-VBM model only
PLFY-WP-VBM model only
PLFY-WP-VFM model only
PLFY-WP-VBM, PLFY-WP-VFM model only
Disabled
The setting depends on the
model and type.
Set to OFF on floor-standing
(PFFY) type units
Note 1. Settings in the shaded areas are factory settings.
*1. Refer to the Installation Manual.
*2.
SW3-5
SW3-6
Vane setting
Vane position
Initial setting
S
etting
S
tandard
S
tandard
Upward position than the standard
Downward position than the standard
Less draft*
3
Less smudging
Set up *
1
Set up *
1
Set up *
1
unused
OFF
OFF
OFF
ON
OFF
ON
ON
ON
*3.
Be careful of smudge on ceiling.
1
1
2
3
1
2
3
0000006450.BOOK 6 ページ 2021年10月26日 火曜日 午後7時2分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......