[2-7 Example System with an MA Remote Controller ]
BS_02_L
chapter 2 -
21
2
Rest
rict
io
ns
2-7-6
System with Multiple HBCs
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group
of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
5) Short-circuit the S (shield) terminal of the terminal block for the cen-
tral control unit (TB7) and the ground terminal (
) on the outdoor
unit whose power jumper was moved from CN41 to CN40.
6) When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
The table above shows the number of transmission boost-
ers that is required by the system with four HBCs. For each
HBC added or subtracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L12 200m [656ft]
L22 200m [656ft]
The maximum piping length between OC and HB is 150 m.
2) Transmission line for centralized control
L31+L32 200m
[656ft]
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1 200m [656ft]
m2+m3 200m [656ft]
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L32+L31+L12 1000 m [3280ft] (500 m [1640ft])
*1
L32+L22 1000 m [3280ft] (500 m [1640ft])
*1
L12+L31+L22 1000 m [3280ft] (500 m [1640ft])
*1
*1 If a given system includes one or more unit or remote
controller that does not support the maximum allow-
able cable distance of 1000 m [3280 ft], the maximum
allowable cable distance in the system will be 500 m
[1640 ft]. Refer to the latest catalog for information on
which units and remote controllers support the maxi-
mum allowable cable distance of 1000 m [3280 ft].
OC
TB3
TB7
S
51
L31
A B S
L32
OC
TB3
TB7
S
53
SW5-1 OFF ON
Move the male connector
from CN41 to CN40
Group
Group
Group
Group
Group
Group
Group
To be left
unconnected
To be connected
M1M2
M1M2
M1M2
M1M2
M1M2
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
IC
TB5
S
TB15
1 2
04
IC
TB5
S
TB15
1 2
06
A1 B2
MA
A1 B2
MA
A1 B2
MA
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
05
03
L12
L22
IC
TB5
S
TB15
1 2
07
IC
TB5
S
TB15
1 2
08
A1 B2
MA
IC
TB5
S
TB15
1 2
09
IC
TB5
S
TB15
1 2
10
A1 B2
MA
A1 B2
MA
HB
HB
TB3
S
52
57
TB3
M1M2 S
HS1
TB3
S
HS1
TB3
S
1
1
2
1
2
2
2
1
2
57
1
1
2
1
1
LC
TB5
S
14
3
2
3
1
Numbers in the square indicate port numbers.
Connection to HBC
54
59
Interlock operation with the ventilation unit
IC
TB5
S
TB15
1 2
11
IC
TB5
S
TB15
1 2
12
A1 B2
MA
61
HS2
TB3
S
1
2
LC
TB5
S
13
1
2
m2
m3
m1
SW5-1 OFF ON
Leave the male
connector on
CN41 as it is.
System
controller
Note1
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
M1M2
Number of transmission booster
(sold separately) required
1 unit
2 units
When the W/WP/WL200 and
W/WP/WL250 models are not in-
cluded in the connected indoor units
25 - 50 units
-
When the W/WP/WL200 and
W/WP/WL250 models are included
in the connected indoor units
19 - 37 units
38 - 50 units
0000006407.BOOK 21 ページ 2021年10月12日 火曜日 午後4時22分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......