[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
BS_07_M
chapter 7 -
39
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-20
Error Code [4220, 4225, 4226] Detail Code 131
1. Error code definition
Low bus voltage at startup (Detail code 131)
2. Error definition and error detection method
When Vdc 289 V is detected just before the inverter operation.
3. Cause, check method and remedy
(1) Inverter main circuit failure
Same as detail code 108 of 4220 error
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
7-6-21
Error Code [4228] Detail Code 101
1. Error code definition
BUS voltage error (Software detection)
2. Error definition and error detection method
"Vdc
≥
425V" or "Vdc
≤
150V" was detected during inverter operation.
3. Cause, check method and remedy
(1) Power-supply environment
Find out if there was a (momentary) power failure.
Check that the voltage across L and N is between 198 and 264 VAC.
Check the power-supply voltage waveform for distortion.
(2) Power-supply board failure
Measure the voltage across TBP and TBN on the power-supply board while the inverter is stopped. Check the following if the
voltage is below 239 V.
1) Check the wiring between FT001/FT002 (power-supply board) and ACL for proper connection.
Make sure the short-circuit pin of CN003 (power-supply board) is properly connected.
2) Turn the power back on, and if the problem persists, replace the power-supply board.
Measure the voltage across TBP and TBN on the power-supply board while the inverter is stopped. Check the following if the
voltage is 239 V or above.
1) Turn the power back on, and if the problem persists, replace the power-supply board.
7-6-22
Error Code [4230] Detail Code 126
1. Error code definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error definition and error detection method
When DCL temperature that equals or exceeds 150
˚
C is detected (applicable to INV37YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Contact failure
Check the connector CNTH on the INV board for proper connection.
(2)
DCL temperature sen-
sor fault
Disconnect the connector (CNTH), and measure the resistance of the DCL tempera-
ture sensor. Replace the DCL temperature sensor if the value is abnormal. Refer to
[3-3 Functions of the Major Components of Outdoor Unit].
(3)
INV board failure
Replace the INV board if the problem persists after the operation is resumed.
0000006452.BOOK 39 ページ 2021年10月27日 水曜日 午前9時38分
Содержание City Multi PURY-EM200YNW-A1
Страница 1: ......
Страница 11: ...GB_BS_01_L 0000006448 BOOK 2 ページ 2021年10月6日 水曜日 午後1時57分 ...
Страница 35: ...GB_BS_02_L 0000006407 BOOK 2 ページ 2021年10月12日 火曜日 午後4時22分 ...
Страница 69: ...GB_BS_03_L 0000006412 BOOK 2 ページ 2021年10月12日 火曜日 午後4時33分 ...
Страница 97: ...GB_BS_04_L 0000006414 BOOK 2 ページ 2021年10月12日 火曜日 午後4時43分 ...
Страница 131: ...GB_BS_05_M 0000006450 BOOK 2 ページ 2021年10月26日 火曜日 午後7時2分 ...
Страница 165: ...GB_BS_06_F2 0000006532 BOOK 2 ページ 2021年10月8日 金曜日 午前11時51分 ...
Страница 173: ...GB_BS_07_M 0000006452 BOOK 4 ページ 2021年10月27日 水曜日 午前9時38分 ...
Страница 267: ...GB_BS_08_L 0000006416 BOOK 4 ページ 2021年10月26日 火曜日 午後5時30分 ...
Страница 451: ...GB_BS_09_F 0000006418 BOOK 2 ページ 2021年10月13日 水曜日 午前10時38分 ...
Страница 469: ...GB_BS_10_M 0000006456 BOOK 2 ページ 2021年10月26日 火曜日 午後7時49分 ...
Страница 502: ......