[2-10 Restrictions on Refrigerant Pipes ]
28
-
chapter 2
BS_02_E
2
Rest
rict
io
ns
(2) Water pipe between Hydro unit and indoor units
1) Hydro unit’s header pipe (Part A’)
2) Water pipe between Hydro unit’s header pipe to indoor unit (Sections a, b, c, d, e, f, g)
* For other indoor units, refer to the indoor unit installation manual.
* The pipe diameter depends on the capacity of indoor units.
Refer to the indoor unit installation manual for details.
2-10-4
Hydro Unit Connection Method
(1) Size of the pipe that fits the standard Hydro unit ports
Hydro unit
Model name
Inlet pipe size
Outlet pipe size
Hydro unit side
CMH-WM250V-A
40A (housing joint)
40A (housing joint)
CMH-WM350V-A
40A (housing joint)
40A (housing joint)
CMH-WM500V-A
50A (housing joint)
50A (housing joint)
Indoor unit
Connection size
Pipe size
Water inlet
Water outlet
Water return
Water out
PEFY-W·VMA
O.D. 22.0 mm
O.D. 22.0 mm
I.D. 20 mm
I.D. 20 mm
A
To outdoor unit
B
End connection (brazing)
C
Hydro unit
D
To main piping
E
Indoor unit
A
C
E
E
E
E
D
B
0000004972.BOOK 28 ページ 2019年5月8日 水曜日 午後2時48分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......