[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
44
-
chapter 7
BS_07_E
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-25
Error Codes [4250, 4255, 4256] Detail Code 101
1. Error code definition
IPM error (Detail code 101)
2. Error definition and error detection method
In the case of 4250
If an overcurrent is detected by the overcurrent detection circuit CT003 (R127 when INV37YC) on the INV board.
In the case of 4255 and 4256
IPM error signal is detected.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Inverter output related
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit]
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Problems]
[8-10-4 Checking the Inverter for Damage at No-Load]
[8-10-5 Checking the Inverter for Damage during Compressor Operation]
[8-10-15 Checking the Installation Conditions]
Check the IGBT module resistance value of the INV board, if no problems are
found.
[8-10-19 Troubleshooting Problems with IGBT Module]
(2)
The model selection
switches (SW5-3 - 5-8) on
the outdoor unit are set
incorrectly.
Check the setting for the model selection switch on the outdoor unit (Dipswitches
SW5-3 - 5-8 on the outdoor unit control board).
For switch settings, refer to the following page(s). [7-9-2 Error Code [7101]]
(3)
Open phase in the power-
supply due to improper
power-supply wiring.
Refer to item (5) in section [6-1 Read before Test Run].
Cause
Check method and remedy
(1)
Fan motor abnormality
Refer to the following page(s). [8-10-7 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems]
(2)
Fan board failure
Refer to the following page(s).
[8-10-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-10-9 Checking the Fan Board for Damage at No Load]
[8-10-10 Checking the Fan Board for Damage with Load]
0000004984.BOOK 44 ページ 2019年5月17日 金曜日 午前8時21分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......