[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
BS_07_E
chapter 7 -
85
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-9-3
Error Code [7102]
1. Error code definition
Wrong number of connected units
2. Error definition and error detection method
The number of connected indoor units is "0" or exceeds the allowable value.
3. Error source, cause, check method and remedy
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Number of indoor units connected to the outdoor
terminal block (TB3) for indoor/ outdoor transmis-
sion lines exceeds limitations described below.
1)
Check whether the number of units
connected to the outdoor terminal
block (TB3) for indoor/ outdoor
transmission lines does not exceed
the limitation. (See (1) and (2) on
the left.)
(2)
Disconnected transmission line of the outdoor unit 2)
Check (2) - (3) on the left.
(3)
Short-circuited transmission line
When (2) and (3) apply, the following display will
appear.
3)
Check whether the transmission
line for the terminal block for cen-
tralized control (TB7) is not con-
nected to the terminal block for the
indoor/outdoor transmission line
(TB3).
ME remote controller
Nothing appears on the remote controller be-
cause it is not powered.
MA remote controller
"HO" or "PLEASE WAIT" blinks.
(4)
The model selection switch (SW5-7) on the out-
door unit is set to OFF. (Normally set to ON)
4)
Check the setting for the model se-
lection switch on the outdoor unit
(Dipswitches SW5-7 on the outdoor
unit control board).
(5)
Outdoor unit address setting error
The outdoor units in the same refrigerant circuit do
not have sequential address numbers.
(6)
Incorrect type of indoor units are connected.
Restriction on the number of units
Number of units
0 or 1
26 : 200 model
32 : 250 models
39 : 300 models
45 : 350 models
50 : 400 models
50 : 450 models
50 : 500 models
1 : (E)M200 - (E)M500YNW models
Total number of
indoor units
Total number of
LOSSNAY units
(During auto
address
start-up only)
Total number of
outdoor units
1
Total number of
hydro units
0000004984.BOOK 85 ページ 2019年5月17日 金曜日 午前8時21分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......