General Overview on LEV Operation
LEV2 (Outdoor unit: Linear expansion valve) is stepping-motor-driven valves that operate by receiving the pulse signals from
the outdoor unit control board.
(1) Outdoor LEV (LEV2)
The valve opening changes according to the number of pulses.
1) Outdoor unit control board and the LEV (Outdoor unit: Linear expansion valve)
2) Pulse signal output and valve operation
3) LEV closing and opening operation
ø4
ø3
ø2
ø1
ø4
ø3
ø2
ø1
Control board
Drive circuit
LEV
M
5
2
1
3
4
6
DC12V
Red
Blue
Orange
Yellow
White
Orange
White
Blue
Yellow
Red
6
5
4
3
2
1
Output state
Output
(phase)
number
1
2
3
4
1
ON OFF OFF ON
2
ON ON OFF OFF
3
OFF ON ON OFF
4
OFF OFF ON ON
Output pulses change in the following orders when the
Valve is closed; 1 2 3 4 1
Valve is open; 4 3 2 1 4
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
*Upon power on, the indoor unit circuit board sends a 2200 pulse
signal to the indoor unit LEV and a 3200 pulse signal to the outdoor
unit LEV to determine the valve position and always brings the valve to
the position as indicated by " A " in the diagram.
When the valve operates smoothly, no sound from LEV or no vibration
occurs, however, when the pulses change from E to A in the chart or
the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by
holding a screwdriver against it, then placing your ear against the handle.
*1 The LEV opening may become greater depending on the operation status.
V
alve opening (refrigerant flow rate)
Valve closed
Valve open
E
B
80 - 100 pulses
Pulses
Fully open
.1400 pulses (indoor unit LEV) *1
.2100 pulses (outdoor unit LEV) *1
A
C
D
0000004986.BOOK 25 ページ 2019年5月9日 木曜日 午後6時22分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......