[2-8 Example System with an ME Remote Controller ]
BS_02_E
chapter 2 -
21
2
Rest
rict
io
ns
2-8
Example System with an ME Remote Controller
2-8-1
System with a Connection of System Controller to Centralized Control
Transmission Line
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot both be
connected to the same group of indoor units.
2) No more than 2 ME remote controllers can be connected to a
group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that
are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be
performed only on one of the outdoor units (not required if power
to the transmission line for centralized control is supplied from a
controller with a power supply function, such as AE-200E).
5) Provide an electrical path to ground for the S terminal on the ter-
minal block for centralized control (TB7) on only one of the out-
door units.
6) A transmission booster must be connected to a system in which
the total number of connected indoor units exceeds 20.
7) A transmission booster is required in a system to which more
than 16 indoor including one or more indoor units of the 200
model or above are connected.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
8) When a power supply unit is connected to the transmission line
for centralized control, leave the power jumper connector on
CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Same as 2-7-3
2) Transmission line for centralized control
Same as 2-7-4
3) M-NET remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16])
m1
10m [32ft]
m2+m3
10m [32ft]
If the standard-supplied cable must be extended, use a cable
with a diameter of 1.25mm
2
[AWG16]. The section of the cable
that exceeds 10m [32ft] must be included in the maximum in-
door-outdoor transmission line distance described in 1).
*When connected to the terminal block on the Simple remote
controller, use cables that meet the following cable size specifi-
cations: 0.75 - 1.25 mm
2
[AWG18-14].
4) Maximum line distance via outdoor unit
(1.25 mm
2
[AWG16] min.)
Same as 2-7-4
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
02
LC
TB5
S
07
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
05
04
LC
TB5
S
08
IC
TB5
S
TB15
1 2
03
IC
TB5
S
TB15
1 2
06
A B
RC
101
A B
RC
102
A B
RC
103
Group
Group
Group
Group
Group
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
104
A B
RC
154
A B
RC
m3
106
A B
RC
m2
Note1 When only the LM adapter is connected,
leave SW5-1 to OFF (as it is).
Note2 LM adapters require the power supply
capacity of single-phase AC 220/240V.
L12
L11
L22
L21
L31
A B S
L32
Note1
System controller
Interlock operation with
the ventilation unit
OC
TB3
TB7
S
51
m1
HU
TB3
52
M1 M2 S
M1 M2
M1 M2
OC
TB3
TB7
S
54
HU
TB3
55
M1 M2 S
M1 M2
M1 M2
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
SW5-1 OFF ON
Move the male connector
from CN41 to CN40.
To be connected
To be left
unconnected
0000004972.BOOK 21 ページ 2019年5月8日 水曜日 午後2時48分
Содержание City Multi CMH-WM250V-A
Страница 1: ......
Страница 11: ...GB_BS_01_G 0000005109 BOOK 2 ページ 2019年5月9日 木曜日 午前10時1分 ...
Страница 37: ...GB_BS_02_E 0000004972 BOOK 2 ページ 2019年5月8日 水曜日 午後2時48分 ...
Страница 67: ...GB_BS_03_E 0000004974 BOOK 2 ページ 2019年5月9日 木曜日 午後6時11分 ...
Страница 91: ...GB_BS_04_E 0000004976 BOOK 2 ページ 2019年5月8日 水曜日 午後2時57分 ...
Страница 119: ...GB_BS_05_E 0000004980 BOOK 2 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 147: ... 5 3 Hydro Unit Control 28 chapter 5 BS_05_E 5 Control 0000004980 BOOK 28 ページ 2019年5月9日 木曜日 午後6時18分 ...
Страница 149: ...GB_BS_06_E 0000004982 BOOK 2 ページ 2019年5月8日 水曜日 午後3時4分 ...
Страница 163: ...GB_BS_07_E 0000004984 BOOK 4 ページ 2019年5月17日 金曜日 午前8時21分 ...
Страница 391: ...GB_BS_09_C 0000005077 BOOK 2 ページ 2019年5月8日 水曜日 午後3時12分 ...
Страница 409: ...GB_BS_10_E 0000004988 BOOK 2 ページ 2019年5月9日 木曜日 午前8時15分 ...
Страница 436: ......